Low Voltage UL/CSA Fuses
Class RK1

A6D-R - Class RK1 - Time-Delay
Amp-Trap 2000 SmartSpot time-delay A6D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A6D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A6D-R fuses can be used to replace obsolete 600V Class H, K or RK5 fuses already installed in the field.
FEATURES
- Solid-state SmartSpot indicator
- Time-delay for motor starting and transformer inrush currents without nuisance opening
- 300kA interrupting rating, self-certified (UL witnessed test
- Extremely current-limiting for low peak let-thru current
- Easy 2-to-1 selectivity for prevention of nuisance shut downs and "black outs"
- Rejection-style design prevents replacement errors (when used with recommended fuse blocks)
- High-visibility orange label gives instant recognition
- Reduced inventory by taking the place of Class RK5, K, and H fuses
- Metal embossed date and catalog number for easier traceability and lasting identification
- Fiberglass body provides dimensional stability in harsh industrial settings
- High-grade silica filler ensures fast arc quenching
PRODUCT DETAILS
- Volts (VAC) 600 VAC
- Volts (VDC) 600 VDC
- Ampere Range (A) 1/10-600 A
- I.R. AC (kA) 200 kA
- I.R DC (kA) 100 kA
-
IR Other (kA)
300kA 600VAC
Self Certified (UL Witnessed) - Class Class RK1
- Speed / Characteristic Time-Delay
- Mounting Clip
-
Connection Terminal Type
Ferrule
Blade -
Body Style
Cylindrical
Rejection - Body Material Polyester
- Materials Contact Tin-plated Copper
-
Standards
UL Listed to Standard 248-12, File E2137
DC Listed to UL Standard 248
CSA Certified to Standard C22.2, No. 248.12 -
Application
Motors
Safety Switches
Transformers
Disconnects
Control Panels
All General-purpose Circuits - ROHS Compliant Consult Technical Services
- Lead Free Consult Technical Services
- CE conformity Consult Technical Services
-
UL File Card
E2137 JDDZ.E2137
-
CSA File Card
Class: 1422-02 File: 012636_0_000
Catalog-Reference
- A6D1-1/4R - D219883
- A6D1-1/8R - V222566
- A6D1-4/10R - L223087
- A6D1-6/10R - R200874
- A6D1-8/10R - D201414
- A6D1/10R - R201932
- A6D1/2R - P211153
- A6D100R - N211152
- A6D10R - G211675
- A6D110R - F211674
- A6D125R - L212185
- A6D12R - M212186
- A6D15/100R - D212707
- A6D150R - C212706
- A6D15R - N213222
- A6D17-1/2R - E213720
- A6D175R - M213221
- A6D1R - M214233
- A6D2-1/2R - Q214742
- A6D2-1/4R - T215251
- A6D2-8/10R - X215760
- A6D2/10R - C216271
- A6D200R - D213719
- A6D20R - C216777
- A6D225R - L214232
- A6D250R - P214741
- A6D25R - Q217295
- A6D2R - V217805
- A6D3-1/2R - F218321
- A6D3-2/10R - T218839
- A6D3/10R - G219357
- A6D300R - S215250
- A6D30R - E219884
- A6D350R - W215759
- A6D35R - W222567
- A6D3R - M223088
- A6D4-1/2R - S200875
- A6D4/10R - E201415
- A6D400R - B216270
- A6D40R - S201933
- A6D450R - B216776
- A6D45R - Q211154
- A6D4R - H211676
- A6D5-6/10R - N212187
- A6D500R - P217294
- A6D50R - E212708
- A6D5R - P213223
- A6D6-1/4R - F213721
- A6D6/10R - N214234
- A6D600R - T217804
- A6D60R - R214743
- A6D6R - V215252
- A6D7/10R
- A6D70R - E218320
- A6D7R - Y215761
- A6D80R - S218838
- A6D8R - R217296
- A6D90R - F219356
- A6D9R - W217806
PERFORMANCE DATA
- A6D(.1-8)R Average Time Current Curve (84 KB)
- A6D(15-30)R Average Time Current Curve (16.3 KB)
- A6D(35-60)R Average Time Current Curve (16.0 KB)
- A6D(70-100)R Average Time Current Curve (73 KB)
- A6D(110-600)R Average Time Current Curve (37 KB)
- A6D(15-30)R Peak Let Thru Curve (51 KB)
- A6D(35-60)R Peak Let Thru Curve (53 KB)
- A6D(70-100)R Peak Let Thru Curve (44 KB)
- A6D(110-600)R Peak Let Thru Curve (52 KB)
Find what you need fast...
Quick Links
- EP Connect
- Product Selector Tools
- Rapid Prototyping
- R-Tools Heatsink Selector Tool
- Contact Us Form
- Quick quote request
- Sample request
- Keep Me Informed
- Compliance