Catalog
Low Voltage UL/CSA Fuses
Midget Fuses

DCT - Midget - Fast-Acting
Amp-Trap DCT fuses were developed to meet requirements coming from new applications such as protection of photovoltaic cells, multi meters and compact on board traction equipment for auxiliary circuits. This high performance DC fuse in its compact size offers multiple competitive advantages particularly for international applications where DC voltage requirements are above 600VDC.
FEATURES
- 1000 VDC with L/R = 1ms
- Low minimum breaking capacity:
- 1A to 7A = 1.3 x In
- 8A to 30A = 2.0 x In
- Compact size: 10 X 38 mm (13/32 X 1-1/2) size internationally accepted.
- Can be used with UltraSafe Fuseholders
PRODUCT DETAILS
- Volts (VAC) 750 VAC
- Volts (VDC) 1000 VDC
- Ampere Range (A) 1-30 A
- I.R. AC (kA) 100 kA
- I.R DC (kA) 50 kA
- Class Midget
- Speed / Characteristic Fast-Acting
- Mounting Clip
- Connection Terminal Type Ferrule
-
Body Style
Cylindrical
Non Rejection - Body Material GMG
- Materials Contact Tin-plated Copper
-
Standards
UL Recognized Component, File E60314, Guide JFHR2
RoHS Compliant -
Application
Multi meters
690V Transformers
DC Traction Equipment - ROHS Compliant Consult Technical Services
- Lead Free Consult Technical Services
- CE conformity Consult Technical Services
-
UL File Card
E60314 JFHR2.E60314
Catalog-Reference
- DCT1-2 - F1011292
- DCT10-2 - L236818
- DCT12-2 - M236819
- DCT15-2 - N236820
- DCT2-2 - P1008724
- DCT20-2 - P236821
- DCT25-2 - Q236822
- DCT3-2 - R1008726
- DCT30-2 - R236823
- DCT4-2 - S1008727
- DCT5-2 - H236815
- DCT6-2 - J236816
- DCT7-2 - S1013189
- DCT8-2 - K236817
PERFORMANCE DATA
- DCT(5-30) Peak Let Thru Curve (23 KB)
- DCT(1-7)-2 Average Time Current Curve (22 KB)
- DCT(8-30)-2 Average Time Current Curve (21 KB)